BACK CALL
ASK A QUESTION
QUESTIONNAIRE

Automatic Transfer Switch devices (ATS)

Application and designated area

Automatic transfer switch ATS is an inlet device intended to receive and distribute alternating electric current of 0.4 kW with frequency 50 Hz to feed consumers of 1st category.
Cover construction provides inlet and outlet of supply and outdoing lines both up and bottom in any combinations.
By Customer’s option, ATS devices can be equipped with surge arresters of class В.
The door is locked.
Installation of hanging devices is (25 — 160А) flexible and is provided with mounting brackets and anchors, mounted via holes in the back wall. Standing devices are fixed via four holes in the bottom with help of anchors.
ATS devices are performed in metal constructions with dimensions complying with rated current and hardware variant of ATS.

Functional features

Operational automatic switching of ATS-100 is performed in case of one, two or three phases missing, in emergency short-circuit modes of the main or protection inlet of power supply network. ATS device consists of a set of inlet, power commutation, distribution, control and signal devices placed in a single-side service casing.
Operational automatic switching of ATS-200 is performed with controlled time delay in case of a phase rotation, asymmetry of phase voltages, missing one or more phases, symmetric voltage drop, emergency short-circuit modes of the main or protection inlet of power supply network.
Operational automatic switching of ATS-300 is performed with controlled time delay basing on operation and protection phase rotation, phase voltage asymmetry, missing one or more phases, symmetric voltage drop, emergency short-circuit modes.
Operational automatic switching of ATS-400 performs the same functions and controls the same supply network parameters as ATS-200. Special feature consists in a higher operation current (1n = 250, 400А).
ATS -500 device performs commutation of loads with controlled time delay basing on phase rotation, missing one or more phases, symmetric or asymmetric voltage drop of supply inlets as well as in short circuit mode.
Special feature of ATS -500 consists in a section unit between equal nonvolatile inlets which helps to perform commutation in parallel operation as a result of an emergency of a one inlet.
ATS -600 device performs the same functions and controls the same supply network parameters as of ATS -500. Special feature consists in two section units.

Specifications

Rated voltage 380/220V, frequency 50 Hz.
rated current up to 1000 А.
climatic categories UЗ, U3.1, UHL4 acc. to GOST 15150-69 and GOST 15543.1-89.
Degree of protection with closed door IP 21, IP 54 (for devices with current up to 160А); for standing devices IP20, from the bottom side IPOO acc. to GOST 14254-96.
Device rated current decreases by 15% when degree of protection of device casing is IP 54.
Inexplosive environment with no current-conducting dust, concentrated aggressive gases or vapors which damage metal and insulation.
Elevation over sea level 2000 m.
Special operation performance — by Customer’s option.
Group of application conditions in part of action of mechanical factors М1 acc. to GOST 17516.1 — 90.
Operation condition — vertical. Allowed deviation of operation conditions not more than 5*.
Safety requirements comply with GOST 12.2.007.0-75 and GOST 22789-94 as well as CEP requirements, Regulations for Operation of Consumer Electrical Installations specified by Minenergo.
Fire requirements comply with GOST 12.1.004-91

Designation structure

ATS -Х Х Х — Х — ХХХ — ХХ ХХ
1   2 3 4      5         6         7    8
1 – Automatic protection switch;
2 – Type of ATS device for unit and commutation controls:
2.1 – two 3 phase inlets, switching if one phase is missing
2.2 – two 3 phase inlets, switching if one phase is missing, voltage decrease of one phase uneven phase rotation;
2.3 – three 3 phase inlets, switching if one phase is missing, voltage decrease of one phase uneven phase rotation;
2.4 – the same as in 2 for currents up to 250-400А;
2.5 – two 3 phase inlets with sectioning, switching if one phase is missing, voltage decrease of one phase uneven phase rotation;
2.6 – two 3 phase inlets with an “eight”, switching if one phase is missing, voltage decrease of one phase uneven phase rotation;
3 – Number of outgoing 3-phase automatic breakers (0 …6);
4 – Number of outgoing 1-phase automatic breakers (0 …18);
5 – Rated current of device; 10 — 10 А; 25 — 25 А; 40 – 40 А; 63 — 63 А; 100 — 100 А; 160 — 160 А; 250 — 250 А; 400 — 400 А
6 — Type of contactor (for ATS 250, 400А): К — КТ60HZ; М — КМ20-ZH;
7 — Cover protection degree acc. to GOST 14254-96: 21 — IP21; 54- IP54;
8 — Climatic and position category complies with GOST 15150-69 and GOST 15543.1-89 — U3, U3.1, UHL4

65

avr-1

avr-2

avr-3

avr-4

avr-5

avr-6

avr-7

Обратный звонок

your-name*

your-email*

number

Задать вопрос

your-name*

your-email *

subject

message

Опросный лист

Опросный лист конденсаторная высоковольтная
Опросный лист конденсаторная низковольтная
Опросный лист КРУ РН
Опросный лист КСО 393В, 393ВЭ, 298, 272, 204, КВ 2003 с вакуумным выключателем
Опросный лист КТП общий
Опросный лист ПКУ
Опросный лист ЯКНО, КРН